AS-i 3.0 Command Interface Commands of the Command Interface
Subject to reasonable modifications due to technical advances Id.-No.: 102875 Issue date - 3.12.2007 EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen Tel. +49/711/7597-0, Fax +49/711/753316
43
4.5 Configuration of AS-i Master
4.5.1 Overview of the commands
4.5.2 Set operation mode (SET_OP_MODE: Set_Operation_Mode)
This call switches between configuration mode and protected mode. In protected
mode, only AS-i slaves entered in the LPS and whose expected and actual con-
figurations match, are being activated.
In other words: The slaves are being activated if the I/O configuration and the ID
codes of the detected AS-i slaves are identical to the configured values.
Response (if O ≡ 1)
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
111
16
2T result
30A1A2A3A4A5A6A7A
……
10 24B 25B 26B 27B 28B 29B 30B 31B
Further diagnosis functions for "Safety at Work" and for availability (resp. for
warnings) of integrated sensors are detailed explained in the chapter "Func-
tional Profiles" (chapter 4.7).
Values for command
see page
Command Value Meaning
Req
Len
Res
Len
page 43 SET_OP_MODE
0C
16
Set_Operation_Mode 3 2
page 44 STORE_CDI
07
16
Store_Actual_Configuration 2 2
page 45 READ_CDI
28
16
Read_Actual_Configuration 3 4
page 45 SET_PCD
25
16
Set_Permanent_Config 5 2
page 45 GET_PCD
26
16
Get_Permanent_Config 3 4
page 47 SET_LPS
29
16
SET_LPS 11 2
page 48 GET_LPS
44
16
Get_LPS 2 10
page 48 STORE_PI
04
16
Store_Actual_Parameter 2 2
page 49 WRITE_P
02
16
Write_Parameter 4 3
page 49 READ_PI
03
16
Read_Parameter 3 3
page 50 SET_PP
43
16
Set_Permanent_Parameter 4 2
page 50 GET_PP
01
16
Get_Permanent_Parameter 3 3
page 51 SET_AAE
0B
16
Set_Auto_Address_Enable 3 2
page 53 SLAVE_ADDR
0D
16
Change_Slave_Address 4 2
page 52 WRITE_XID1
3F
16
Write_Extended_ID-Code_1 3 2
Comentários a estes Manuais