
Operating Instructions Evaluation Unit CES-A-V1B-04B-AS1
Subject to technical modifications; no responsibility is accepted for the accuracy of this information. (c) EUCHNER GmbH + Co. KG 103138-02-05/12 (translation of the original operating instructions)
Configuration in the AS-Interface safety
monitor (refer to the operating instructions for the
AS-Interface safety monitor)
The safety switch is configured in the AS-Interface
safety monitor with the AS-Interface address set as
follows, for example:
f dual-channel dependent
f without start-up test
f synchronization time = 0.5 seconds
AS-Interface status messages
The ASI PWR (green) and FAULT (red) LED indicators
indicate the status messages on the AS-Interface
bus. The following table provides assistance with
troubleshooting.
LED state
Explanation
ASI PWR
Green
FAULT
RED
on off Normal operation
on on
No data exchange between master and
slave
Cause:
- Master in the STOP mode
- Slave not in LPS
- Slave with incorrect IO/ID
- Reset active on the slave
flashing on
No data exchange between master and
slave
Cause: Slave address =0
flashing flashing
Device fault in the slave.
Contact EUCHNER.
on flashing
Function test
f Close the safety guard.
f Start the machine.
f Machine must stop immediately when the safety
guard is opened!
f Switch off the machine.
f Open the safety guard.
f The machine must not start when the safety guard
is open!
Service and inspection
No servicing is required on the battery-less actuator,
but regular inspection of the following is necessary
to ensure trouble-free long-term operation:
f Secure fastening of the actuator and the read head
(use of safety screws included)
f Sealing of the plug connector on the evaluation unit
f Loose cable connections on the evaluation unit
f Switch-off distance check
f A function test should be performed at least once
a year.
f Shorter intervals may be necessary depending on
the specific application.
Exclusion of liability under the following
circumstances
f if the unit is not used for its intended purpose
f non-compliance with safety regulations
f mounting and electrical connection not performed
by authorized personnel
f non-implementation of functional checks
f if modifications are made.
Programming State D0, D1 D2, D3 Monitor diagnosis
2-channel
dependent
Synchronization
time
0.5 s
Safety guard closed Code sequence
Safe
Green in ASIMON
Safety guard open,
transponder
only half-read
Half-sequence 00
Not safe
Yellow flashing
in ASIMON
Safety guard open,
transponder
only half-read
00 Half-sequence
Not safe
Yellow flashing
in ASIMON
Safety guard open 00 00
Not safe
Red in ASIMON
Address 0 or
communication disrupted
–
Gray
Table 2: Troubleshooting
With the read heads CES, CEM and CET, two processors each read the transponder in the actuator. Fasten-
ing the actuator in the operating distance with small hysteresis can lead to even slight vibrations causing
the transponder to be read by only one processor (half-reading). This causes the ”yellow flashing“ state to
be indicated.
It is recommended to fasten the actuator in the operating distance so that the hysteresis is adequately large
(Figure 3). If this cannot be realized, the ”dual-channel dependent with filtering“ module can be used in the
ASIMON software. More detailed information about this can be found in the ASIMON software manual, which
can be opened via the Help function of the ASIMON software.
Bit sequence on
AS-Interface bus
LED STATE
(green)
LED OUT/ERROR
(yellow)
LED OUT/ERROR
(red)
State
Normal operation
safe code
sequence
on on off All monitored doors are closed
0000 on off off All monitored doors are not closed
0000 off off on
Device-internal component failure or
excessively high external interference (EMC) or
actuator in the operating distance for less than 0.5 s
0000 flashing 15 Hz off off
Self-test after connecting to the AS-Interface bus
Duration approx. 10 s
Initial setup
0000
flashing 4 Hz
continuously
off off Initial setup, ready for teach-in operation
0000 flashing 1 Hz off off Teach-in operation
0000 off off off Teach-in operation complete, switch off device for setup
Operating fault
0000
continuous
flashing 3 times
off on
Configuration fault:
Teach-in operation must be performed again.
Possible causes:
- State change during the teach-in operation
- None of the DIP switches in ON position
- DIP switch setting and connected configuration did not match during teach-in
operation
- DIP switch setting has been changed without teach-in operation
- DIP switch for the teach-in mode changed with power supply switched on
Table 1: System states
Comentários a estes Manuais